ITAC Assessment: AR0018
ITAC logo
ITAC Assessment: AR0018
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1994
Principal Product Steel Pipes & Tubes
NAICS
n/a
SIC 3317: Steel Pipe and Tubes
Sales Range $10
M
to 50
M
# of Employees 260
Plant Area 135,000
ft2
Annual Production 3,600,000
lb
Production Hrs. Annual 6,257
hrs
Location (State) Arkansas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $572,852 9,497,362
kWh
Natural Gas $17,125 3,920
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $95,657 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $29,741

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $10,756 $800 $10,756
178,195
kWh
02 2.7111: Reduce illumination to minimum necessary levels $5,336 $1,140 $5,336
88,511
kWh
03 2.7142: Utilize higher efficiency lamps and/or ballasts $1,883 $533 $1,883
31,360
kWh
04 2.4221: Install compressor air intakes in coolest locations $6,234 $350 $6,234
103,458
kWh
05 2.7243: Improve air circulation with destratification fans / other methods $5,532 $5,850 $5,532
91,735
kWh
06 2.7232: Replace existing hvac unit with high efficiency model $38,242 $143,000 $38,242
633,939
kWh
07 2.4231: Reduce the pressure of compressed air to the minimum required $500 $250 $500
8,206
kWh
08 2.3131: Reschedule plant operations or reduce load to avoid peaks $4,672 $400 $4,672
-
kWh
09 2.3212: Optimize plant power factor $22,502 $10,950 $22,502
-
kWh
TOTAL RECOMMENDED $95,657 $163,273 $95,657
1,135,404
kWh
TOTAL IMPLEMENTED $29,741 $8,673 $29,741
493,259
kWh
Yearly Savings* Imp'd Cost* Electricity Usage Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs