| Assessment Year | 2026 |
|---|---|
| Principal Product | Waste Water Treatment |
| NAICS | 221320: Sewage Treatment Facilities |
| SIC | 4952: Sewerage Systems |
| Sales Range | less than $500 k |
| # of Employees | 5 |
| Plant Area |
23,000
ft2
|
| Annual Production | 25,500
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $810,000 | 10,500,000 |
kWh
|
$0.077 | |
| Electricity Fees | $1,360 | - |
|
- | |
| Waste Disposal Costs | |||||
| Water Usage | $1,820 | 20,600 |
Tgal
|
$0.088 | |
| TOTAL YEARLY COSTS | $813,180 | ||||
| RECOMMENDED SAVINGS* | $318,035 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4322: Use or replace with energy efficient substitutes | $149,000 | $33,800 |
$149,000
1,940,000
kWh
|
- | |
| 02 | 2.6231: Utilize controls to operate equipment only when needed | $129,000 | $372,000 |
$129,000
1,780,000
kWh
|
- | |
| 03 | 2.9114: Use solar heat to make electricty | $26,400 | $582,100 |
$26,400
336,000
kWh
|
- | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $10,500 | - |
$10,500
136,000
kWh
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,135 | $27,400 |
$2,500
32,400
kWh
|
$635 | |
| TOTAL RECOMMENDED | $318,035 | $1,015,300 |
$317,400
4,224,400
kWh
|
$635 | ||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs