| Assessment Year | 2026 |
|---|---|
| Principal Product | pre-engineered metal building |
| NAICS | 332322: Sheet Metal Work Manufacturing |
| SIC | 1761: Roofing, Siding, and Sheet Metal Work |
| Sales Range | $50 M to 100M |
| # of Employees | 205 |
| Plant Area |
480,000
ft2
|
| Annual Production | 27,000
ton
|
| Production Hrs. Annual | 7,180
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $138,000 | 2,070,000 |
kWh
|
$0.067 |
| Electricity Demand | $58,800 | 6,000 |
kW-mo/yr
|
$9.80 |
| Electricity Fees | $20,500 | - |
|
- |
| Natural Gas | $2,130 | 210 |
MMBtu
|
$10.14 |
| TOTAL YEARLY COSTS | $219,430 | |||
| RECOMMENDED SAVINGS* | $200,521 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $34,800 | $39,900 | - |
$34,800
-
kW-mo/yr
|
- | - | |
| 02 | 2.8121: Apply for tax-free status for energy purchases | $75,200 | $15,000 | - | - | $18,800 | $56,400 | |
| 03 | 2.4224: Upgrade controls on compressors | $8,550 | $30,260 |
$6,740
101,000
kWh
|
$1,810
-
kW-mo/yr
|
- | - | |
| 04 | 2.7243: Improve air circulation with destratification fans / other methods | $3,590 | $27,890 |
$2,440
36,400
kWh
|
$1,150
-
kW-mo/yr
|
- | - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $756 | $231 |
$472
7,050
kWh
|
$284
-
kW-mo/yr
|
- | - | |
| 06 | 2.4314: Use synthetic lubricant | $625 | $610 |
$372
5,560
kWh
|
$253
-
kW-mo/yr
|
- | - | |
| 07 | 2.9114: Use solar heat to make electricty | $77,000 | $1,465,000 |
$77,000
1,150,000
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $200,521 | $1,578,891 |
$87,024
1,300,010
kWh
|
$38,297
-
kW-mo/yr
|
$18,800 | $56,400 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs