Assessment Year | 2021 |
---|---|
Principal Product | water |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | $1 M to 5M |
# of Employees | 30 |
Plant Area |
50,000
ft2
|
Annual Production | 1,095,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $43,716 | 1,182,980 |
kWh
|
$0.037 |
Electricity Demand | $18,364 | 2,270 |
kW-mo/yr
|
$8.09 |
Electricity Fees | $1,450 | - |
|
- |
TOTAL YEARLY COSTS | $63,530 | |||
RECOMMENDED SAVINGS* | $15,775 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,775 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $7,250 | $1,000 |
$7,250
196,000
kWh
|
- | - | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,970 | $4,220 |
$2,260
61,000
kWh
|
$710
-
kW-mo/yr
|
- | - | - | |
03 | 2.3212: Optimize plant power factor | $2,250 | $3,410 | - |
$2,250
-
kW-mo/yr
|
- | - | - | |
04 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,980 | $150 |
$1,220
32,900
kWh
|
$760
-
kW-mo/yr
|
- | - | - | |
05 | 2.7135: Install occupancy sensors | $750 | $510 |
$750
20,200
kWh
|
- | - | - | - | |
06 | 2.4156: Establish a preventative maintenance program | $475 | $2,250 |
$555
15,000
kWh
|
$170
-
kW-mo/yr
|
- | $(-810.0) | $560 | |
07 | 2.8112: Combine utility meters | $100 | $17 | - | - | $100 | - | - | |
TOTAL RECOMMENDED | $15,775 | $11,557 |
$12,035
325,100
kWh
|
$3,890
-
kW-mo/yr
|
$100 | $(-810.0) | $560 | ||
TOTAL IMPLEMENTED | $15,775 | $11,557 |
$12,035
325,100
kWh
|
$3,890
-
kW-mo/yr
|
$100 | $(-810.0) | $560 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs