Assessment Year | 2015 |
---|---|
Principal Product | Steel fabrication |
NAICS | 332313: Plate Work Manufacturing |
SIC | 3443: Fabricated Plate Work (Boiler Shops) |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
200,000
ft2
|
Annual Production | 2,000,000
lb
|
Production Hrs. Annual | 2,730
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $79,678 | 1,224,790 |
kWh
|
$0.065 |
Electricity Demand | $70,115 | 6,456 |
kW-mo/yr
|
$10.86 |
Electricity Fees | $6,614 | - |
|
- |
Natural Gas | $30,370 | 7,637 |
MMBtu
|
$3.98 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $44,770 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $33,595 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4226: Use / purchase optimum sized compressor | $10,100 | $5,270 |
$6,460
101,690
kWh
|
$3,640
-
kW-mo/yr
|
- | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $14,595 | $4,000 | - | - | $9,690 | $4,905 | |
03 | 2.3212: Optimize plant power factor | $8,425 | $12,120 | - |
$8,425
-
kW-mo/yr
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,740 | $1,840 |
$4,300
67,645
kWh
|
$2,440
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,780 | $3,990 |
$1,070
16,800
kWh
|
$710
-
kW-mo/yr
|
- | - | |
06 | 2.7145: Install skylights | $1,770 | $5,300 |
$1,770
27,910
kWh
|
- | - | - | |
07 | 2.7135: Install occupancy sensors | $980 | $1,170 |
$980
15,380
kWh
|
- | - | - | |
08 | 2.7124: Make a practice of turning off lights when not needed | $380 | - |
$280
4,410
kWh
|
$100
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $44,770 | $33,690 |
$14,860
233,835
kWh
|
$15,315
-
kW-mo/yr
|
$9,690 | $4,905 | ||
TOTAL IMPLEMENTED | $33,595 | $15,100 |
$12,110
190,545
kWh
|
$6,890
-
kW-mo/yr
|
$9,690 | $4,905 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs