ITAC Assessment: AM0669
ITAC logo
ITAC Assessment: AM0669
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2014
Principal Product Aluminum beverage cans
NAICS 332431: Metal Can Manufacturing
SIC 3411: Metal Cans
Sales Range $100
M
to 500
M
# of Employees 402
Plant Area 260,000
ft2
Annual Production 2,255,500,000
pieces
Production Hrs. Annual 8,328
hrs
Location (State) Texas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,728,079 44,809,250
kWh
Electricity Demand $585,434 70,656
kW-mo/yr
Electricity Fees $86,380 -
Natural Gas $643,774 135,213
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $75,338 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $70,538

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Consumption Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $24,407 $52 $16,421
453,769
kWh
$7,986
-
kW-mo/yr
-
02 3.4155: Meter waste water $20,590 $4,500 - - $20,590
-
Tgal
03 2.4111: Utilize energy-efficient belts and other improved mechanisms $10,410 - $7,300
201,900
kWh
$3,110
-
kW-mo/yr
-
04 2.7124: Make a practice of turning off lights when not needed $6,332 $3,600 $4,724
130,533
kWh
$1,608
-
kW-mo/yr
-
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $5,663 $12,000 $5,663
156,475
kWh
- -
06 2.6231: Utilize controls to operate equipment only when needed $4,800 $315 $3,560
98,396
kWh
$1,240
-
kW-mo/yr
-
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,186 $570 $1,630
45,034
kWh
$556
-
kW-mo/yr
-
08 2.7111: Reduce illumination to minimum necessary levels $950 $44 $711
19,654
kWh
$239
-
kW-mo/yr
-
TOTAL RECOMMENDED $75,338 $21,081 $40,009
1,105,761
kWh
$14,739
-
kW-mo/yr
$20,590
-
Tgal
TOTAL IMPLEMENTED $70,538 $20,766 $36,449
1,007,365
kWh
$13,499
-
kW-mo/yr
$20,590
-
Tgal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs