Assessment Year | 2014 |
---|---|
Principal Product | Aluminum beverage cans |
NAICS | 332431: Metal Can Manufacturing |
SIC | 3411: Metal Cans |
Sales Range | $100 M to 500M |
# of Employees | 402 |
Plant Area |
260,000
ft2
|
Annual Production | 2,255,500,000
pieces
|
Production Hrs. Annual | 8,328
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,728,079 | 44,809,250 |
kWh
|
$0.039 |
Electricity Demand | $585,434 | 70,656 |
kW-mo/yr
|
$8.29 |
Electricity Fees | $86,380 | - |
|
- |
Natural Gas | $643,774 | 135,213 |
MMBtu
|
$4.76 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $75,338 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $70,538 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $24,407 | $52 |
$16,421
453,769
kWh
|
$7,986
-
kW-mo/yr
|
- | |
02 | 3.4155: Meter waste water | $20,590 | $4,500 | - | - |
$20,590
-
Tgal
|
|
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $10,410 | - |
$7,300
201,900
kWh
|
$3,110
-
kW-mo/yr
|
- | |
04 | 2.7124: Make a practice of turning off lights when not needed | $6,332 | $3,600 |
$4,724
130,533
kWh
|
$1,608
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,663 | $12,000 |
$5,663
156,475
kWh
|
- | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $4,800 | $315 |
$3,560
98,396
kWh
|
$1,240
-
kW-mo/yr
|
- | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,186 | $570 |
$1,630
45,034
kWh
|
$556
-
kW-mo/yr
|
- | |
08 | 2.7111: Reduce illumination to minimum necessary levels | $950 | $44 |
$711
19,654
kWh
|
$239
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $75,338 | $21,081 |
$40,009
1,105,761
kWh
|
$14,739
-
kW-mo/yr
|
$20,590
-
Tgal
|
||
TOTAL IMPLEMENTED | $70,538 | $20,766 |
$36,449
1,007,365
kWh
|
$13,499
-
kW-mo/yr
|
$20,590
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs