Assessment Year 2012
Principal Product Injection molded plastic packaging
NAICS 326130: Laminated Plastics Plate, Sheet (except Packaging), and Shape Manufacturing
SIC 3083: Laminated Plastics Plate, Sheet, and Profile Shapes
Sales Range $50
M
to 100
M
# of Employees 172
Plant Area 175,000
ft2
Annual Production 480,000
thousand feet
Production Hrs. Annual 6,000
hrs
Location (State) Louisiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $717,554 10,280,000
kWh
Electricity Demand $5,407 24,956
kW-mo/yr
Electricity Fees $52,840 -
Natural Gas $116,791 17,177
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $60,118 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $45,318

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.4133: Use most efficient type of electric motors $21,010 $38,103 $18,472
342,079
kWh
$2,538
-
kW-mo/yr
-
02 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available $16,300 $20,900 $14,300
264,600
kWh
$2,000
-
kW-mo/yr
-
03 2.7261: Install timers and/or thermostats $14,800 $2,230 - - $14,800
-
MMBtu
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,265 $600 $3,840
71,116
kWh
$425
-
kW-mo/yr
-
05 2.7134: Use photocell controls $3,000 $1,000 $3,000
54,900
kWh
- -
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $694 $108 $608
11,267
kWh
$86
-
kW-mo/yr
-
07 2.7134: Use photocell controls $49 $100 $49
900
kWh
- -
TOTAL RECOMMENDED $60,118 $63,041 $40,269
744,862
kWh
$5,049
-
kW-mo/yr
$14,800
-
MMBtu
TOTAL IMPLEMENTED $45,318 $60,811 $40,269
744,862
kWh
$5,049
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs