Assessment Year | 2007 |
---|---|
Principal Product | Pipe Threading |
NAICS | 332996: Fabricated Pipe and Pipe Fitting Manufacturing |
SIC | 3498: Fabricated Pipe and Pipe Fittings |
Sales Range | $50 M to 100M |
# of Employees | 225 |
Plant Area |
156,000
ft2
|
Annual Production | 120,000
pieces
|
Production Hrs. Annual | 7,390
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $489,732 | 6,248,796 |
kWh
|
$0.078 |
Electricity Demand | $102,785 | 14,955 |
kW-mo/yr
|
$6.87 |
Electricity Fees | $38,096 | - |
|
- |
Natural Gas | $110,596 | 12,375 |
MMBtu
|
$8.94 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $277,920 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $273,230 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $98,110 | $155,442 |
$87,240
1,014,400
kWh
|
$10,870
-
kW-mo/yr
|
- | - | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $163,900 | - | - | - | $37,900 | - | $126,000 | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,600 | $700 |
$5,000
58,100
kWh
|
$600
-
kW-mo/yr
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,395 | $1,350 |
$590
6,870
kWh
|
$55
-
kW-mo/yr
|
- | $2,750 | - | |
05 | 2.7145: Install skylights | $3,340 | - |
$3,540
41,200
kWh
|
- | - | $(-200.0) | - | |
06 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,750 | - |
$1,750
20,400
kWh
|
- | - | - | - | |
07 | 2.4314: Use synthetic lubricant | $1,350 | - |
$1,180
13,700
kWh
|
$170
-
kW-mo/yr
|
- | - | - | |
08 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $475 | $65 |
$395
4,600
kWh
|
$80
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $277,920 | $157,557 |
$99,695
1,159,270
kWh
|
$11,775
-
kW-mo/yr
|
$37,900 | $2,550 | $126,000 | ||
TOTAL IMPLEMENTED | $273,230 | $157,557 |
$94,975
1,104,370
kWh
|
$11,605
-
kW-mo/yr
|
$37,900 | $2,750 | $126,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs