Assessment Year | 1997 |
---|---|
Principal Product | blowers and fans |
NAICS |
n/a
|
SIC | 3564: Industrial and Commercial Fans and Blowers and Air Purification Equipment |
Sales Range | $1 M to 5M |
# of Employees | 35 |
Plant Area |
31,780
ft2
|
Annual Production | 63,250
pieces
|
Production Hrs. Annual | 2,598
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $27,671 | 643,611 |
kWh
|
$0.043 |
Electricity Demand | $27,255 | 4,292 |
kW-mo/yr
|
$6.35 |
Natural Gas | $3,153 | 670 |
MMBtu
|
$4.71 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $7,920 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,240 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 3.2123: Convert to high volume low pressure (hvlp) paint guns | $4,080 | $295 | - | - | - | - |
$4,080
-
lb
|
- | |
02 | 2.6218: Turn off equipment when not in use | $800 | - |
$340
7,913
kWh
|
$460
-
kW-mo/yr
|
- | - | - | - | |
03 | 4.231: Purchase equipment instead of leasing | $610 | - | - | - | - | - | - | $610 | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $540 | $300 |
$540
12,603
kWh
|
- | - | - | - | - | |
05 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $520 | - |
$520
12,016
kWh
|
- | - | - | - | - | |
06 | 3.7131: Use a rag recycle service | $470 | $33 | - | - | - | - | - | $470 | |
07 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $220 | - | - | - | - | - |
$220
-
lb
|
- | |
08 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $210 | - |
$210
4,689
kWh
|
- | - | - | - | - | |
09 | 2.7124: Make a practice of turning off lights when not needed | $180 | - |
$180
4,103
kWh
|
- | - | - | - | - | |
10 | 3.8133: Convert to aqueous cleaning | $150 | - | - | - |
$(-220.0)
-
gal
|
$370
-
gal
|
- | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $140 | $70 |
$80
1,758
kWh
|
$60
-
kW-mo/yr
|
- | - | - | - | |
TOTAL RECOMMENDED | $7,920 | $698 |
$1,870
43,082
kWh
|
$520
-
kW-mo/yr
|
$(-220.0)
-
gal
|
$370
-
gal
|
$4,300
-
lb
|
$1,080 | ||
TOTAL IMPLEMENTED | $6,240 | $595 |
$1,090
25,205
kWh
|
$460
-
kW-mo/yr
|
- | - |
$4,080
-
lb
|
$610 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs