Assessment Year | 1992 |
---|---|
Principal Product | TACOS,TAQUITOS,BURRITOS |
NAICS |
n/a
|
SIC | 2038: Frozen Specialties, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 100 |
Plant Area |
n/a
|
Annual Production | 26,000,000
lb
|
Production Hrs. Annual | 4,080
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $661,720 | 11,453,400 |
kWh
|
$0.058 |
Natural Gas | $146,485 | 70,401 |
MMBtu
|
$2.08 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $43,863 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $32,033 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.2121: Increase amount of condensate returned | $13,280 | $6,775 | - |
$4,630
-
MMBtu
|
$8,650 | |
02 | 2.2511: Insulate bare equipment | $7,250 | $1,670 |
$7,250
135,698
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,150 | $11,940 |
$5,150
100,234
kWh
|
- | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $4,970 | $500 |
$4,970
114,009
kWh
|
- | - | |
05 | 2.6232: Install set-back timers | $4,360 | $200 |
$4,360
99,941
kWh
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,370 | $325 |
$3,370
77,374
kWh
|
- | - | |
07 | 2.4133: Use most efficient type of electric motors | $2,433 | $3,150 |
$2,433
44,842
kWh
|
- | - | |
08 | 2.2414: Use waste heat from hot flue gases to preheat | $1,820 | $3,500 | - |
$1,820
-
MMBtu
|
- | |
09 | 2.2531: Re-size charging openings or add movable cover or door | $730 | $4,800 | - |
$730
-
MMBtu
|
- | |
10 | 2.6232: Install set-back timers | $500 | $400 |
$500
11,723
kWh
|
- | - | |
TOTAL RECOMMENDED | $43,863 | $33,260 |
$28,033
583,821
kWh
|
$7,180
-
MMBtu
|
$8,650 | ||
TOTAL IMPLEMENTED | $32,033 | $17,220 |
$18,023
371,923
kWh
|
$5,360
-
MMBtu
|
$8,650 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs