Assessment Year | 2015 |
---|---|
Principal Product | Beverages |
NAICS | 311920: Coffee and Tea Manufacturing |
SIC | 2043: Cereal Breakfast Foods |
Sales Range | $50 M to 100M |
# of Employees | 95 |
Plant Area |
140,000
ft2
|
Annual Production | 26,600,000
pieces
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $981,041 | 15,690,000 |
kWh
|
$0.063 |
Electricity Demand | $177,205 | 36,529 |
kW-mo/yr
|
$4.85 |
Natural Gas | $1,623,755 | 247,717 |
MMBtu
|
$6.55 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $151,546 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $50,572 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $53,712 | $100,740 |
$53,712
859,390
kWh
|
- | - | - | |
02 | 2.7231: Use radiant heater for spot heating | $45,555 | $130,520 | - | - |
$45,555
-
MMBtu
|
- | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $16,058 | $1,700 | - | - |
$16,126
-
MMBtu
|
$(-68.0) | |
04 | 2.4157: Establish a predictive maintenance program | $10,550 | $1,000 |
$12,187
194,990
kWh
|
$1,576
-
kW-mo/yr
|
- | $(-3,213.0) | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,891 | $599 |
$6,989
111,828
kWh
|
$902
-
kW-mo/yr
|
- | - | |
06 | 2.2511: Insulate bare equipment | $6,111 | $6,377 | - | - |
$6,111
-
MMBtu
|
- | |
07 | 2.4151: Develop a repair/replace policy | $5,821 | $864 |
$5,876
94,013
kWh
|
$761
-
kW-mo/yr
|
- | $(-816.0) | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,141 | $19,874 |
$3,302
52,837
kWh
|
$839
-
kW-mo/yr
|
- | - | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,537 | - |
$1,362
21,799
kWh
|
$175
-
kW-mo/yr
|
- | - | |
10 | 2.4239: Eliminate or reduce compressed air usage | $170 | $457 |
$151
2,412
kWh
|
$19
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $151,546 | $262,131 |
$83,579
1,337,269
kWh
|
$4,272
-
kW-mo/yr
|
$67,792
-
MMBtu
|
$(-4,097.0) | ||
TOTAL IMPLEMENTED | $50,572 | $30,414 |
$28,354
453,668
kWh
|
$4,078
-
kW-mo/yr
|
$22,237
-
MMBtu
|
$(-4,097.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs