Assessment Year | 1997 |
---|---|
Principal Product | Diaphragms, Gauges, Transducers |
NAICS |
n/a
|
SIC | 3829: Measuring and Controlling Devices, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 450 |
Plant Area |
180,000
ft2
|
Annual Production | 3,900,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $173,614 | 6,278,136 |
kWh
|
$0.028 |
Electricity Demand | $111,641 | 12,850 |
kW-mo/yr
|
$8.69 |
Natural Gas | $148,605 | 21,834 |
MMBtu
|
$6.81 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $1,329,997 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $14,979 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,328 | $484 |
$1,981
71,512
kWh
|
$1,347
-
kW-mo/yr
|
- | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $3,793 | $3,114 |
$943
33,998
kWh
|
$2,850
-
kW-mo/yr
|
- | - | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $63 | $30 |
$63
2,345
kWh
|
- | - | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $1,037 | $417 |
$1,037
37,515
kWh
|
- | - | - | - | |
05 | 2.4314: Use synthetic lubricant | $907 | $615 |
$907
32,825
kWh
|
- | - | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,795 | $200 |
$1,795
64,771
kWh
|
- | - | - | - | |
07 | 2.7241: Install outside air damper / economizer on hvac unit | $2,252 | $1,175 |
$2,252
81,477
kWh
|
- | - | - | - | |
08 | 2.2437: Recover waste heat from equipment | $4,386 | $1,000 | - | - |
$4,386
-
MMBtu
|
- | - | |
09 | 2.1213: Direct warmest air to combustion intake | $2,683 | $3,740 | - | - |
$2,683
-
MMBtu
|
- | - | |
10 | 2.1123: Install automatic stack damper | $3,753 | $1,600 | - | - |
$3,753
-
MMBtu
|
- | - | |
11 | 2.6212: Turn off equipment during breaks, reduce operating time | $453 | - |
$45
1,758
kWh
|
- |
$408
-
MMBtu
|
- | - | |
12 | 3.5313: Increase amount of waste recovered for resale | $1,387 | - | - | - | - | $1,387 | - | |
13 | 3.5316: Contract a wood pallet recycling company | $4,160 | $200 | - | - | - | $4,160 | - | |
14 | 4.652: Replace existing equipment with more suitable substitutes | $1,300,000 | $125,000 | - | - | - | - | $1,300,000 | |
TOTAL RECOMMENDED | $1,329,997 | $137,575 |
$9,023
326,201
kWh
|
$4,197
-
kW-mo/yr
|
$11,230
-
MMBtu
|
$5,547 | $1,300,000 | ||
TOTAL IMPLEMENTED | $14,979 | $4,028 |
$4,827
174,384
kWh
|
$4,197
-
kW-mo/yr
|
$408
-
MMBtu
|
$5,547 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs