Assessment Year | 1995 |
---|---|
Principal Product | Glass and Vinyl windows |
NAICS |
n/a
|
SIC | 3442: Metal Doors, Sash, Frames, Molding, and Trim Manufacturing |
Sales Range | $10 M to 50M |
# of Employees | 310 |
Plant Area |
93,000
ft2
|
Annual Production | 600,000
pieces
|
Production Hrs. Annual | 4,080
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $141,896 | 2,462,778 |
kWh
|
$0.058 |
Natural Gas | $20,197 | 2,346 |
MMBtu
|
$8.61 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $8,698 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,612 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,509 | $2,400 |
$3,509
82,063
kWh
|
- | |
02 | 2.7224: Reduce space conditioning during non-working hours | $778 | $360 | - |
$778
-
MMBtu
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,308 | $15 |
$3,308
77,374
kWh
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,103 | - |
$1,103
25,791
kWh
|
- | |
TOTAL RECOMMENDED | $8,698 | $2,775 |
$7,920
185,228
kWh
|
$778
-
MMBtu
|
||
TOTAL IMPLEMENTED | $4,612 | $2,400 |
$4,612
107,854
kWh
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs