| Assessment Year | 1994 |
|---|---|
| Principal Product | Automotive metal stampings |
| NAICS |
n/a
|
| SIC | 3465: Automotive Stampings |
| Sales Range | $50 M to 100M |
| # of Employees | 485 |
| Plant Area |
977,000
ft2
|
| Annual Production | 96,000
ton
|
| Production Hrs. Annual | 8,568
hrs
|
| Location (State) | West Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $890,138 | 24,318,875 |
kWh
|
$0.037 |
| Natural Gas | $180,814 | 54,074 |
MMBtu
|
$3.34 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $47,139 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $4,694 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $42 | $331 |
$42
1,172
kWh
|
|
| 02 | 2.4133: Use most efficient type of electric motors | $701 | $42,700 |
$701
21,395
kWh
|
|
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,462 | $4,000 |
$8,462
259,965
kWh
|
|
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $16,486 | - |
$16,486
506,448
kWh
|
|
| 05 | 2.7134: Use photocell controls | $8,983 | $9,600 |
$8,983
276,084
kWh
|
|
| 06 | 2.7241: Install outside air damper / economizer on hvac unit | $7,813 | $1,267 |
$7,813
240,035
kWh
|
|
| 07 | 2.4314: Use synthetic lubricant | $4,652 | - |
$4,652
143,025
kWh
|
|
| TOTAL RECOMMENDED | $47,139 | $57,898 |
$47,139
1,448,124
kWh
|
||
| TOTAL IMPLEMENTED | $4,694 | $331 |
$4,694
144,197
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs