| Assessment Year | 1994 |
|---|---|
| Principal Product | Engine Bearings |
| NAICS |
n/a
|
| SIC | 3562: Ball and Roller Bearings |
| Sales Range | $50 M to 100M |
| # of Employees | 545 |
| Plant Area |
225,000
ft2
|
| Annual Production | 85,000,000
thousand feet
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $924,746 | 24,960,141 |
kWh
|
$0.037 |
| Natural Gas | $201,962 | 36,499 |
MMBtu
|
$5.53 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $20,000 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $11,909 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,806 | $15,603 |
$2,806
47,773
kWh
|
- | |
| 02 | 2.4133: Use most efficient type of electric motors | $1,312 | $29,510 |
$1,312
7,620
kWh
|
- | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $6,240 | $452 |
$6,240
176,143
kWh
|
- | |
| 04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,526 | $1,000 | - |
$1,526
-
MMBtu
|
|
| 05 | 2.2136: Install / repair insulation on steam lines | $325 | $116 | - |
$325
-
MMBtu
|
|
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,432 | - |
$4,432
125,147
kWh
|
- | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,359 | $200 |
$3,359
94,959
kWh
|
- | |
| TOTAL RECOMMENDED | $20,000 | $46,881 |
$18,149
451,642
kWh
|
$1,851
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $11,909 | $45,313 |
$11,909
275,499
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs