Assessment Year 2023
Principal Product Plastic Sheets
NAICS 326112: Plastics Packaging Film and Sheet (including Laminated) Manufacturing
SIC 3081: Unsupported Plastics Film and Sheet
Sales Range $50
M
to 100
M
# of Employees 125
Plant Area 185,600
ft2
Annual Production 34,694,588
lb
Production Hrs. Annual 8,112
hrs
Location (State) Wisconsin

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $697,217 11,271,600
kWh
Electricity Demand $253,485 23,580
kW-mo/yr
Electricity Fees $76,812 -
Natural Gas $197,942 24,710
MMBtu
Waste Disposal Costs
Water Usage $36,906 1,956
Tgal
TOTAL YEARLY COSTS $1,262,362
RECOMMENDED SAVINGS* $50,574 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $24,776

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $15,725 $13,127 $13,493
217,622
kWh
$2,233
-
kW-mo/yr
- - -
02 2.7231: Use radiant heater for spot heating $15,091 $13,400 - - $15,091
-
MMBtu
- -
03 2.7211: Clean and maintain refrigerant condensers and towers $5,128 $1,700 $4,081
65,826
kWh
$1,047
-
kW-mo/yr
- - -
04 2.3131: Reschedule plant operations or reduce load to avoid peaks $4,436 $3,735 - - - $4,436 -
05 4.821: Pay bills on time to avoid late fees $2,687 - - - - - $2,687
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $2,381 $700 $2,110
34,040
kWh
$271
-
kW-mo/yr
- - -
07 2.7135: Install occupancy sensors $1,997 $1,000 $1,730
27,903
kWh
$267
-
kW-mo/yr
- - -
08 2.7212: Install or upgrade insulation on hvac distribution systems $1,986 $2,700 - - $1,986
-
MMBtu
- -
09 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,142 $1,715 $1,012
16,329
kWh
$130
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $50,574 $38,077 $22,427
361,720
kWh
$3,947
-
kW-mo/yr
$17,077
-
MMBtu
$4,436 $2,687
TOTAL IMPLEMENTED $24,776 $17,527 $17,333
279,565
kWh
$2,770
-
kW-mo/yr
$1,986
-
MMBtu
- $2,687
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs