Assessment Year | 2023 |
---|---|
Principal Product | Plastic Sheets |
NAICS | 326112: Plastics Packaging Film and Sheet (including Laminated) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $50 M to 100M |
# of Employees | 125 |
Plant Area |
185,600
ft2
|
Annual Production | 34,694,588
lb
|
Production Hrs. Annual | 8,112
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $697,217 | 11,271,600 |
kWh
|
$0.062 | |
Electricity Demand | $253,485 | 23,580 |
kW-mo/yr
|
$10.75 | |
Electricity Fees | $76,812 | - |
|
- | |
Natural Gas | $197,942 | 24,710 |
MMBtu
|
$8.01 | |
Waste Disposal Costs | |||||
Water Usage | $36,906 | 1,956 |
Tgal
|
$18.87 | |
TOTAL YEARLY COSTS | $1,262,362 | ||||
RECOMMENDED SAVINGS* | $50,574 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $24,776 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,725 | $13,127 |
$13,493
217,622
kWh
|
$2,233
-
kW-mo/yr
|
- | - | - | |
02 | 2.7231: Use radiant heater for spot heating | $15,091 | $13,400 | - | - |
$15,091
-
MMBtu
|
- | - | |
03 | 2.7211: Clean and maintain refrigerant condensers and towers | $5,128 | $1,700 |
$4,081
65,826
kWh
|
$1,047
-
kW-mo/yr
|
- | - | - | |
04 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $4,436 | $3,735 | - | - | - | $4,436 | - | |
05 | 4.821: Pay bills on time to avoid late fees | $2,687 | - | - | - | - | - | $2,687 | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,381 | $700 |
$2,110
34,040
kWh
|
$271
-
kW-mo/yr
|
- | - | - | |
07 | 2.7135: Install occupancy sensors | $1,997 | $1,000 |
$1,730
27,903
kWh
|
$267
-
kW-mo/yr
|
- | - | - | |
08 | 2.7212: Install or upgrade insulation on hvac distribution systems | $1,986 | $2,700 | - | - |
$1,986
-
MMBtu
|
- | - | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,142 | $1,715 |
$1,012
16,329
kWh
|
$130
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $50,574 | $38,077 |
$22,427
361,720
kWh
|
$3,947
-
kW-mo/yr
|
$17,077
-
MMBtu
|
$4,436 | $2,687 | ||
TOTAL IMPLEMENTED | $24,776 | $17,527 |
$17,333
279,565
kWh
|
$2,770
-
kW-mo/yr
|
$1,986
-
MMBtu
|
- | $2,687 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs