| Assessment Year | 2019 |
|---|---|
| Principal Product | Printed Circuit Board Assemblies |
| NAICS | 334419: Other Electronic Component Manufacturing |
| SIC | 3679: Electronic Components, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 65 |
| Plant Area |
22,280
ft2
|
| Annual Production | 1,000,000
pieces
|
| Production Hrs. Annual | 5,000
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $69,351 | 825,600 |
kWh
|
$0.084 | |
| Electricity Demand | $14,399 | 1,986 |
kW-mo/yr
|
$7.25 | |
| Electricity Fees | $(-3,487.0) | - |
|
- | |
| Natural Gas | $4,163 | 595 |
MMBtu
|
$7.00 | |
| Waste Disposal Costs | |||||
| Water Usage | $8,171 | 209 |
Tgal
|
$39.17 | |
| TOTAL YEARLY COSTS | $92,597 | ||||
| RECOMMENDED SAVINGS* | $32,414 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $23,987 | $106,000 |
$23,987
285,565
kWh
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,803 | $4,811 |
$3,730
44,410
kWh
|
$1,073
-
kW-mo/yr
|
- | |
| 03 | 2.7313: Recycle air for heating, ventilation and air conditioning | $1,529 | $1,319 |
$1,187
14,135
kWh
|
$341
-
kW-mo/yr
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $854 | $1,600 |
$663
7,896
kWh
|
$191
-
kW-mo/yr
|
- | |
| 05 | 2.7224: Reduce space conditioning during non-working hours | $692 | - | - | - |
$692
-
MMBtu
|
|
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $549 | - |
$387
4,599
kWh
|
$162
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $32,414 | $113,730 |
$29,955
356,605
kWh
|
$1,768
-
kW-mo/yr
|
$692
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs