| Assessment Year | 2018 |
|---|---|
| Principal Product | Wastewater Treatment |
| NAICS | 221320: Sewage Treatment Facilities |
| SIC | 4952: Sewerage Systems |
| Sales Range | less than $500 k |
| # of Employees | 10 |
| Plant Area |
1,004,191
ft2
|
| Annual Production | 2,920,000
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $292,183 | 6,691,080 |
kWh
|
$0.044 | |
| Electricity Demand | $126,305 | 12,217 |
kW-mo/yr
|
$10.34 | |
| Electricity Fees | $6,174 | - |
|
- | |
| Natural Gas | $18,059 | 3,091 |
MMBtu
|
$5.84 | |
| Waste Disposal Costs | |||||
| Water Usage | $580 | 37 |
Tgal
|
$15.63 | |
| TOTAL YEARLY COSTS | $443,301 | ||||
| RECOMMENDED SAVINGS* | $29,549 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $13,310 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $11,827 | $48,514 |
$11,827
270,829
kWh
|
- | - | - | |
| 02 | 2.4314: Use synthetic lubricant | $6,420 | $5,000 |
$4,848
111,007
kWh
|
$1,572
-
kW-mo/yr
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,995 | $4,950 |
$1,650
37,800
kWh
|
$2,345
-
kW-mo/yr
|
- | - | |
| 04 | 2.7221: Lower temperature during the winter season and vice-versa | $2,831 | - | - | - |
$2,831
-
MMBtu
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,722 | $950 |
$2,055
47,057
kWh
|
$667
-
kW-mo/yr
|
- | - | |
| 06 | 2.7231: Use radiant heater for spot heating | $1,581 | $3,820 | - | - |
$1,581
-
MMBtu
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $173 | $345 |
$106
2,418
kWh
|
$34
-
kW-mo/yr
|
- | $33 | |
| TOTAL RECOMMENDED | $29,549 | $63,579 |
$20,486
469,111
kWh
|
$4,618
-
kW-mo/yr
|
$4,412
-
MMBtu
|
$33 | ||
| TOTAL IMPLEMENTED | $13,310 | $11,245 |
$8,659
198,282
kWh
|
$4,618
-
kW-mo/yr
|
- | $33 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs