Assessment Year | 2017 |
---|---|
Principal Product | Treated Wastewater and Salable Fertilizer |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4953: Refuse Systems |
Sales Range | $100 M to 500M |
# of Employees | 232 |
Plant Area |
3,000,000
ft2
|
Annual Production | 70,000,000
Tgal
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $564,652 | 9,997,843 |
kWh
|
$0.056 | |
Electricity Demand | $310,076 | 22,936 |
kW-mo/yr
|
$13.52 | |
Electricity Fees | $193,595 | - |
|
- | |
Natural Gas | $5,914,140 | 1,579,742 |
MMBtu
|
$3.74 | |
Waste Disposal Costs | |||||
Water Usage | $211,980 | 119,364 |
Tgal
|
$1.78 | |
TOTAL YEARLY COSTS | $7,194,443 | ||||
RECOMMENDED SAVINGS* | $268,427 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $135,557 | $350,000 |
$135,557
1,847,585
kWh
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $38,256 | $90,000 |
$38,256
677,335
kWh
|
- | - | |
03 | 2.4314: Use synthetic lubricant | $30,600 | $7,500 |
$23,028
407,723
kWh
|
$7,572
-
kW-mo/yr
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $24,084 | $45,000 |
$18,136
321,127
kWh
|
$5,948
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $23,424 | $56,250 |
$17,638
312,374
kWh
|
$5,786
-
kW-mo/yr
|
- | |
06 | 2.2622: Replace existing chiller with high efficiency model | $16,506 | $73,860 |
$12,383
219,240
kWh
|
$2,771
-
kW-mo/yr
|
$1,352 | |
TOTAL RECOMMENDED | $268,427 | $622,610 |
$244,998
3,785,384
kWh
|
$22,077
-
kW-mo/yr
|
$1,352 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs