Assessment Year | 2016 |
---|---|
Principal Product | Medical Carts & Electronic Enclosures |
NAICS | 332322: Sheet Metal Work Manufacturing |
SIC | 3444: Sheet Metal Work |
Sales Range | $10 M to 50M |
# of Employees | 121 |
Plant Area |
150,000
ft2
|
Annual Production | 194,963
units
|
Production Hrs. Annual | 4,080
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $153,256 | 2,120,539 |
kWh
|
$0.072 |
Electricity Demand | $91,649 | 7,203 |
kW-mo/yr
|
$12.72 |
Electricity Fees | $4,010 | - |
|
- |
Natural Gas | $68,726 | 20,511 |
MMBtu
|
$3.35 |
TOTAL YEARLY COSTS | $317,641 | |||
RECOMMENDED SAVINGS* | $32,042 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,051 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $12,568 | $2,860 | - | - |
$12,568
-
MMBtu
|
- | |
02 | 2.8112: Combine utility meters | $8,777 | $30,000 | - | - | - | $8,777 | |
03 | 2.7135: Install occupancy sensors | $2,746 | $1,275 |
$2,746
38,385
kWh
|
- | - | - | |
04 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $2,722 | - |
$2,722
38,052
kWh
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,051 | $230 |
$1,351
18,887
kWh
|
$700
-
kW-mo/yr
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,795 | $1,501 |
$877
12,265
kWh
|
$917
-
kW-mo/yr
|
- | - | |
07 | 2.7134: Use photocell controls | $1,383 | $560 |
$899
12,659
kWh
|
$484
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $32,042 | $36,426 |
$8,596
120,248
kWh
|
$2,101
-
kW-mo/yr
|
$12,568
-
MMBtu
|
$8,777 | ||
TOTAL IMPLEMENTED | $2,051 | $230 |
$1,351
18,887
kWh
|
$700
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs