| Assessment Year | 2016 |
|---|---|
| Principal Product | Drain tile, custom blow molding |
| NAICS | 326122: Plastics Pipe and Pipe Fitting Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 25 |
| Plant Area |
50,000
ft2
|
| Annual Production | 2,000,000
pieces
|
| Production Hrs. Annual | 6,500
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $165,351 | 2,782,789 |
kWh
|
$0.059 |
| Electricity Demand | $51,253 | 7,192 |
kW-mo/yr
|
$7.13 |
| Electricity Fees | $32,053 | - |
|
- |
| Natural Gas | $10,392 | 1,391 |
MMBtu
|
$7.47 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $21,163 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,723 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4314: Use synthetic lubricant | $4,146 | $4,500 |
$3,366
56,642
kWh
|
$780
-
kW-mo/yr
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,385 | $1,225 |
$3,385
56,977
kWh
|
- | - | |
| 03 | 2.4314: Use synthetic lubricant | $3,352 | $1,507 |
$2,483
41,785
kWh
|
$869
-
kW-mo/yr
|
- | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,109 | $780 |
$2,524
42,481
kWh
|
$585
-
kW-mo/yr
|
- | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,338 | - |
$1,953
32,872
kWh
|
$385
-
kW-mo/yr
|
- | |
| 06 | 2.7111: Reduce illumination to minimum necessary levels | $2,275 | $1,589 |
$1,840
30,968
kWh
|
$435
-
kW-mo/yr
|
- | |
| 07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,246 | $1,600 |
$2,246
37,791
kWh
|
- | - | |
| 08 | 2.2136: Install / repair insulation on steam lines | $312 | $122 | - | - |
$312
-
MMBtu
|
|
| TOTAL RECOMMENDED | $21,163 | $11,323 |
$17,797
299,516
kWh
|
$3,054
-
kW-mo/yr
|
$312
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $5,723 | $1,225 |
$5,338
89,849
kWh
|
$385
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs