Assessment Year | 2015 |
---|---|
Principal Product | water meters |
NAICS | 334514: Totalizing Fluid Meter and Counting Device Manufacturing |
SIC | 3824: Totalizing Fluid Meters and Counting Devices |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
315,000
ft2
|
Annual Production | 100,000,000
pieces
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $506,902 | 8,081,774 |
kWh
|
$0.063 |
Electricity Demand | $236,470 | 17,853 |
kW-mo/yr
|
$13.25 |
Natural Gas | $81,910 | 12,757 |
MMBtu
|
$6.42 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $92,658 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $31,723 | $105,982 |
$24,137
384,837
kWh
|
$7,586
-
kW-mo/yr
|
- | - | |
02 | 2.4314: Use synthetic lubricant | $14,981 | $4,505 |
$14,981
238,860
kWh
|
- | - | - | |
03 | 2.3212: Optimize plant power factor | $11,162 | $18,000 | - |
$11,162
-
kW-mo/yr
|
- | - | |
04 | 3.4111: Use closed cycle process to minimize waste water production | $10,083 | $3,000 | - | - |
$7,453
-
Tgal
|
$2,630
-
gal
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,459 | $11,985 |
$7,203
114,840
kWh
|
$257
-
kW-mo/yr
|
- | - | |
06 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $4,749 | $8,000 |
$3,359
53,550
kWh
|
$1,391
-
kW-mo/yr
|
- | - | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,708 | $400 |
$3,708
59,118
kWh
|
- | - | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $2,724 | $2,584 |
$1,929
30,762
kWh
|
$795
-
kW-mo/yr
|
- | - | |
09 | 2.7134: Use photocell controls | $2,082 | $2,816 |
$846
13,496
kWh
|
$1,236
-
kW-mo/yr
|
- | - | |
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,824 | $1,300 |
$1,290
20,564
kWh
|
$534
-
kW-mo/yr
|
- | - | |
11 | 2.7111: Reduce illumination to minimum necessary levels | $1,156 | $300 |
$813
12,960
kWh
|
$343
-
kW-mo/yr
|
- | - | |
12 | 2.7135: Install occupancy sensors | $1,006 | $1,500 |
$780
12,434
kWh
|
$226
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $92,658 | $160,372 |
$59,046
941,421
kWh
|
$23,529
-
kW-mo/yr
|
$7,453
-
Tgal
|
$2,630
-
gal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Other Liquid (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs