Assessment Year | 2015 |
---|---|
Principal Product | Exterior and interior signage |
NAICS | 339950: Sign Manufacturing |
SIC | 3993: Signs and Advertising Specialties |
Sales Range | $10 M to 50M |
# of Employees | 130 |
Plant Area |
88,982
ft2
|
Annual Production | 100,000
units
|
Production Hrs. Annual | 2,700
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $70,114 | 973,535 |
kWh
|
$0.072 |
Electricity Demand | $50,204 | 3,744 |
kW-mo/yr
|
$13.41 |
Electricity Fees | $8,240 | - |
|
- |
Natural Gas | $63,424 | 13,663 |
MMBtu
|
$4.64 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $37,678 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,583 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $2,192 | - | - | - | - | $2,192 | |
02 | 4.512: Condense operation into one building | $2,174 | - |
$1,611
22,364
kWh
|
$563
-
kW-mo/yr
|
- | - | |
03 | 2.6211: Conserve energy by efficient use of vending machines | $1,126 | $860 |
$898
12,462
kWh
|
$228
-
kW-mo/yr
|
- | - | |
04 | 2.7135: Install occupancy sensors | $1,763 | $305 |
$965
13,392
kWh
|
$798
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,746 | $6,310 |
$2,290
31,796
kWh
|
$456
-
kW-mo/yr
|
- | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,738 | $15,750 |
$3,083
42,803
kWh
|
$2,655
-
kW-mo/yr
|
- | - | |
07 | 2.2437: Recover waste heat from equipment | $19,530 | $50,000 | - | - |
$19,530
-
MMBtu
|
- | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $784 | $225 |
$435
6,044
kWh
|
$349
-
kW-mo/yr
|
- | - | |
09 | 2.7212: Install or upgrade insulation on hvac distribution systems | $1,625 | $1,774 |
$1,625
22,558
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $37,678 | $75,224 |
$10,907
151,419
kWh
|
$5,049
-
kW-mo/yr
|
$19,530
-
MMBtu
|
$2,192 | ||
TOTAL IMPLEMENTED | $4,583 | $1,999 |
$3,671
50,966
kWh
|
$912
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs