| Assessment Year | 2003 |
|---|---|
| Principal Product | Aluminum Beverage Cans |
| NAICS | 332431: Metal Can Manufacturing |
| SIC | 3411: Metal Cans |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
n/a
|
| Annual Production | 1,800,000,000
pieces
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $901,448 | 22,914,965 |
kWh
|
$0.039 |
| Electricity Demand | $34,723 | 36,684 |
kW-mo/yr
|
$0.95 |
| Electricity Fees | $55,542 | - |
|
- |
| Natural Gas | $380,922 | 80,237 |
MMBtu
|
$4.75 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $215,328 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $188,665 | $146,300 |
$352,968
9,240,000
kWh
|
$113,520
-
kW-mo/yr
|
$(-277,823.0)
-
MMBtu
|
|
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $16,332 | $6,498 |
$12,926
338,386
kWh
|
$3,406
-
kW-mo/yr
|
- | |
| 03 | 2.3137: Use power during off-peak periods | $5,132 | - | - |
$5,132
-
kW-mo/yr
|
- | |
| 04 | 2.2414: Use waste heat from hot flue gases to preheat | $2,640 | $10,000 | - | - |
$2,640
-
MMBtu
|
|
| 05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,559 | $500 | - | - |
$2,559
-
MMBtu
|
|
| TOTAL RECOMMENDED | $215,328 | $163,298 |
$365,894
9,578,386
kWh
|
$122,058
-
kW-mo/yr
|
$(-272,624.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs