Assessment Year 1992
Principal Product FROZEN VEGETABLES
NAICS
n/a
SIC 2038: Frozen Specialties, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 400
Plant Area
n/a
Annual Production 28,145,200
lb
Production Hrs. Annual 6,000
hrs
Location (State) Illinois

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,302,245 19,467,175
kWh
Natural Gas $138,897 51,756
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $100,442 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $3,192

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
01 2.3132: Recharge batteries on during off-peak demand periods $60,075 $8,000 $60,075
-
kWh
- -
02 2.6232: Install set-back timers $14,417 $1,200 $14,417
215,416
kWh
- -
03 2.7142: Utilize higher efficiency lamps and/or ballasts $721 $148 $1,263
18,757
kWh
- $(-542.0)
04 2.6232: Install set-back timers $1,822 $2,800 $1,822
27,257
kWh
- -
05 2.3131: Reschedule plant operations or reduce load to avoid peaks $9,437 - $10,589
-
kWh
- $(-1,152.0)
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $4,912 $5,362 $4,912
73,564
kWh
- -
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,051 - $1,051
15,826
kWh
- -
08 2.1233: Analyze flue gas for proper air/fuel ratio $3,192 $500 - $3,192
-
MMBtu
-
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,890 - $1,890
28,136
kWh
- -
10 2.2437: Recover waste heat from equipment $1,662 $1,000 - $1,662
-
MMBtu
-
11 2.7226: Use computer programs to optimize hvac performance $1,263 $3,500 $1,263
18,757
kWh
- -
TOTAL RECOMMENDED $100,442 $22,510 $97,282
397,713
kWh
$4,854
-
MMBtu
$(-1,694.0)
TOTAL IMPLEMENTED $3,192 $500 - $3,192
-
MMBtu
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs