Assessment Year | 1988 |
---|---|
Principal Product | PRINTING |
NAICS |
n/a
|
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
n/a
|
Annual Production | 37,000,000
pieces
|
Production Hrs. Annual | 4,750
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $310,428 | 3,453,986 |
kWh
|
$0.090 |
Natural Gas | $60,565 | 16,773 |
MMBtu
|
$3.61 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $30,495 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,368 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4312: Improve lubrication practices | $9,403 | - |
$9,403
104,631
kWh
|
- | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,715 | - |
$4,715
52,462
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,405 | $196 |
$11,405
126,905
kWh
|
- | - | |
04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $220 | $500 | - |
$320
-
MMBtu
|
$(-100.0) | |
05 | 2.7229: Air condition only space necessary | $1,625 | $2,500 | - |
$1,625
-
MMBtu
|
- | |
06 | 2.3191: Use demand controller or load shedder | $3,127 | $5,000 |
$3,127
-
kWh
|
- | - | |
TOTAL RECOMMENDED | $30,495 | $8,196 |
$28,650
283,998
kWh
|
$1,945
-
MMBtu
|
$(-100.0) | ||
TOTAL IMPLEMENTED | $27,368 | $3,196 |
$25,523
283,998
kWh
|
$1,945
-
MMBtu
|
$(-100.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs