| Assessment Year | 2009 |
|---|---|
| Principal Product | Treated Paper Products |
| NAICS | 322219: Other Paperboard Container Manufacturing |
| SIC | 2655: Fiber Cans, Tubes, Drums, and Similar Products |
| Sales Range | less than $500 k |
| # of Employees | 26 |
| Plant Area |
51,000
ft2
|
| Annual Production | 50,000
thousand feet
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Washington |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $143,138 | 2,686,950 |
kWh
|
$0.053 |
| Electricity Fees | $7,619 | - |
|
- |
| Natural Gas | $5,608 | 425 |
MMBtu
|
$13.20 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $27,310 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,312 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $9,632 | $10,324 |
$9,632
163,274
kWh
|
|
| 02 | 2.2622: Replace existing chiller with high efficiency model | $6,650 | $37,000 |
$6,650
112,718
kWh
|
|
| 03 | 2.2511: Insulate bare equipment | $5,716 | $871 |
$5,716
87,600
kWh
|
|
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,168 | $2,280 |
$5,168
87,600
kWh
|
|
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $144 | - |
$144
2,453
kWh
|
|
| TOTAL RECOMMENDED | $27,310 | $50,475 |
$27,310
453,645
kWh
|
||
| TOTAL IMPLEMENTED | $5,312 | $2,280 |
$5,312
90,053
kWh
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs