Assessment Year | 2008 |
---|---|
Principal Product | Plastic and Cardboard Packaging |
NAICS | 322212: Folding Paperboard Box Manufacturing |
SIC | 2657: Folding Paperboard Boxes, Including Sanitary |
Sales Range | $1 M to 5M |
# of Employees | 14 |
Plant Area |
16,000
ft2
|
Annual Production | 50,000
units
|
Production Hrs. Annual | 2,210
hrs
|
Location (State) | Hawaii |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $27,080 | 318,461 |
kWh
|
$0.085 |
Electricity Demand | $7,796 | 1,359 |
kW-mo/yr
|
$5.74 |
Electricity Fees | $21,959 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $17,204 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4321: Upgrade obsolete equipment | $14,766 | $42,706 |
$12,509
72,305
kWh
|
$2,257
-
kW-mo/yr
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,107 | $3,180 |
$931
5,291
kWh
|
$176
-
kW-mo/yr
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,010 | - |
$856
4,946
kWh
|
$154
-
kW-mo/yr
|
|
04 | 2.6211: Conserve energy by efficient use of vending machines | $321 | $189 |
$321
1,825
kWh
|
- | |
TOTAL RECOMMENDED | $17,204 | $46,075 |
$14,617
84,367
kWh
|
$2,587
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs