| Assessment Year | 2007 |
|---|---|
| Principal Product | Kitchen and bath cabinets |
| NAICS | 337110: Wood Kitchen Cabinet and Countertop Manufacturing |
| SIC | 2434: Wood Kitchen Cabinets |
| Sales Range | $50 M to 100M |
| # of Employees | 750 |
| Plant Area |
214,000
ft2
|
| Annual Production | 250,000
pieces
|
| Production Hrs. Annual | 4,680
hrs
|
| Location (State) | Washington |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $347,812 | 6,157,271 |
kWh
|
$0.056 |
| Electricity Demand | $51,423 | 15,405 |
kW-mo/yr
|
$3.34 |
| Natural Gas | $269,513 | 24,732 |
MMBtu
|
$10.90 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $74,730 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $58,875 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $24,804 | $7,172 |
$24,804
442,135
kWh
|
- | - | - | - | |
| 02 | 2.5115: Reposition oven walls to reduce heated space | $15,876 | $4,452 |
$9,401
167,581
kWh
|
$1,557
-
kW-mo/yr
|
$4,918
-
MMBtu
|
- | - | |
| 03 | 2.2531: Re-size charging openings or add movable cover or door | $3,246 | $1,162 | - | - |
$3,246
-
MMBtu
|
- | - | |
| 04 | 2.6127: Maintain air filters by cleaning or replacement | $8,530 | $1,852 |
$5,667
101,021
kWh
|
- | - | $1,010 | $1,853 | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $9,388 | $2,619 |
$8,054
143,562
kWh
|
$1,334
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.3212: Optimize plant power factor | $6,971 | $17,098 | - |
$6,971
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.4239: Eliminate or reduce compressed air usage | $3,766 | $432 |
$3,232
57,626
kWh
|
$534
-
kW-mo/yr
|
- | - | - | |
| 08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,795 | $398 |
$1,539
27,432
kWh
|
$256
-
kW-mo/yr
|
- | - | - | |
| 09 | 2.6211: Conserve energy by efficient use of vending machines | $354 | $650 |
$338
6,023
kWh
|
$16
-
kW-mo/yr
|
- | - | - | |
| TOTAL RECOMMENDED | $74,730 | $35,835 |
$53,035
945,380
kWh
|
$10,668
-
kW-mo/yr
|
$8,164
-
MMBtu
|
$1,010 | $1,853 | ||
| TOTAL IMPLEMENTED | $58,875 | $16,235 |
$47,030
838,336
kWh
|
$3,681
-
kW-mo/yr
|
$8,164
-
MMBtu
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | |||