Assessment Year 2026
Principal Product N/A
NAICS 921120: Legislative Bodies
SIC 8111: Legal Services
Sales Range less than $500
k
# of Employees 425
Plant Area 166,000
ft2
Annual Production 1
units
Production Hrs. Annual 8,760
hrs
Location (State) Utah

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $35,050 967,280
kWh
Electricity Demand $63,178 3,866
kW-mo/yr
Electricity Fees $40,990 -
Natural Gas $9,141 2,670
MMBtu
TOTAL YEARLY COSTS $148,359
RECOMMENDED SAVINGS* $29,810 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
01 2.7423: Reduce heat gain by window tinting $1,490 $16,005 $1,490
38,200
kWh
- -
02 2.9114: Use solar heat to make electricty $22,870 $435,150 $15,200
422,080
kWh
$7,670
-
kW-mo/yr
-
03 2.3212: Optimize plant power factor $2,580 $16,075 - - $2,580
04 2.7314: Reduce ventilation air $2,870 $7,210 $2,870
79,260
kWh
- -
TOTAL RECOMMENDED $29,810 $474,440 $19,560
539,540
kWh
$7,670
-
kW-mo/yr
$2,580
TOTAL IMPLEMENTED - - - - -
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs