| Assessment Year | 2025 |
|---|---|
| Principal Product | Outpatient Clinic |
| NAICS | 621498: All Other Outpatient Care Centers |
| SIC | 8093: Specialty Outpatient Facilities, Not Elsewhere Classified |
| Sales Range | less than $500 k |
| # of Employees | 130 |
| Plant Area |
138,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 3,360
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $119,613 | 3,294,600 |
kWh
|
$0.036 |
| Electricity Demand | $125,142 | 7,618 |
kW-mo/yr
|
$16.43 |
| Electricity Fees | $85,908 | - |
|
- |
| Natural Gas | $95,688 | 19,201 |
MMBtu
|
$4.98 |
| TOTAL YEARLY COSTS | $426,351 | |||
| RECOMMENDED SAVINGS* | $68,124 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $900 | $1,050 |
$325
8,960
kWh
|
$575
-
kW-mo/yr
|
- | |
| 02 | 2.2622: Replace existing chiller with high efficiency model | $9,414 | $47,500 |
$6,227
171,530
kWh
|
$3,187
-
kW-mo/yr
|
- | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,230 | $17,500 |
$1,176
32,360
kWh
|
$2,054
-
kW-mo/yr
|
- | |
| 04 | 2.7229: Air condition only space necessary | $54,580 | $163,800 |
$10,389
286,200
kWh
|
$18,345
-
kW-mo/yr
|
$25,846
-
MMBtu
|
|
| TOTAL RECOMMENDED | $68,124 | $229,850 |
$18,116
499,050
kWh
|
$24,162
-
kW-mo/yr
|
$25,846
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs