| Assessment Year | 2022 |
|---|---|
| Principal Product | Fluid seals |
| NAICS | 339991: Gasket, Packing, and Sealing Device Manufacturing |
| SIC | 3053: Gaskets, Packing, and Sealing Devices |
| Sales Range | $5 M to 10M |
| # of Employees | 300 |
| Plant Area |
130,000
ft2
|
| Annual Production | 90,000,000
pieces
|
| Production Hrs. Annual | 8,757
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $297,928 | 8,800,200 |
kWh
|
$0.034 |
| Electricity Demand | $254,511 | 17,256 |
kW-mo/yr
|
$14.75 |
| Electricity Fees | $154,328 | - |
|
- |
| Natural Gas | $26,722 | 2,915 |
MMBtu
|
$9.17 |
| TOTAL YEARLY COSTS | $733,489 | |||
| RECOMMENDED SAVINGS* | $92,452 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.6218: Turn off equipment when not in use | $45,240 | $17,600 |
$45,240
1,330,600
kWh
|
- | |
| 02 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $13,275 | $12,600 | - |
$13,275
-
kW-mo/yr
|
|
| 03 | 2.2314: Replace heat treating oven with more efficient unit | $10,674 | $25,650 |
$6,426
188,997
kWh
|
$4,248
-
kW-mo/yr
|
|
| 04 | 2.4322: Use or replace with energy efficient substitutes | $7,347 | $5,215 |
$2,489
73,200
kWh
|
$4,858
-
kW-mo/yr
|
|
| 05 | 2.4224: Upgrade controls on compressors | $4,414 | $1,000 |
$4,414
129,827
kWh
|
- | |
| 06 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $4,228 | $2,448 |
$2,651
77,991
kWh
|
$1,577
-
kW-mo/yr
|
|
| 07 | 2.4322: Use or replace with energy efficient substitutes | $2,552 | $4,497 |
$1,338
39,354
kWh
|
$1,214
-
kW-mo/yr
|
|
| 08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,260 | $3,781 |
$2,260
66,470
kWh
|
- | |
| 09 | 2.4235: Remove or close off unneeded compressed air lines | $1,637 | $1,536 |
$1,637
48,155
kWh
|
- | |
| 10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $825 | $900 |
$825
24,274
kWh
|
- | |
| TOTAL RECOMMENDED | $92,452 | $75,227 |
$67,280
1,978,868
kWh
|
$25,172
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs