Assessment Year | 2020 |
---|---|
Principal Product | Water Distribution |
NAICS | 221310: Water Supply and Irrigation Systems |
SIC | 4941: Water Supply |
Sales Range | $5 M to 10M |
# of Employees | 10 |
Plant Area |
13,500
ft2
|
Annual Production | 7,500,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $169,807 | 5,054,406 |
kWh
|
$0.034 |
Electricity Demand | $74,608 | 10,752 |
kW-mo/yr
|
$6.94 |
Electricity Fees | $38,546 | - |
|
- |
TOTAL YEARLY COSTS | $282,961 | |||
RECOMMENDED SAVINGS* | $69,244 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $44,792 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $39,976 | $124,680 |
$31,140
929,551
kWh
|
$8,836
-
kW-mo/yr
|
|
02 | 2.3322: Use existing dam to generate electricity | $24,451 | $120,000 |
$13,210
394,445
kWh
|
$11,241
-
kW-mo/yr
|
|
03 | 2.2211: Use optimum temperature | $4,303 | - |
$3,341
99,734
kWh
|
$961
-
kW-mo/yr
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $514 | $2,100 |
$406
12,100
kWh
|
$108
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $69,244 | $246,780 |
$48,097
1,435,830
kWh
|
$21,147
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $44,792 | $126,780 |
$34,887
1,041,385
kWh
|
$9,905
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs