| Assessment Year | 2020 |
|---|---|
| Principal Product | Drinking water |
| NAICS | 221310: Water Supply and Irrigation Systems |
| SIC | 4941: Water Supply |
| Sales Range | $1 M to 5M |
| # of Employees | 5 |
| Plant Area |
97,000
ft2
|
| Annual Production | 6,520,000
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $116,538 | 3,150,890 |
kWh
|
$0.037 |
| Electricity Demand | $123,417 | 7,408 |
kW-mo/yr
|
$16.66 |
| Electricity Fees | $20,000 | - |
|
- |
| TOTAL YEARLY COSTS | $259,955 | |||
| RECOMMENDED SAVINGS* | $7,772 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7221: Lower temperature during the winter season and vice-versa | $4,252 | $2,000 |
$4,252
116,176
kWh
|
- | |
| 02 | 2.6218: Turn off equipment when not in use | $1,660 | $500 | - |
$1,660
-
kW-mo/yr
|
|
| 03 | 2.7241: Install outside air damper / economizer on hvac unit | $865 | $2,038 |
$615
16,816
kWh
|
$250
-
kW-mo/yr
|
|
| 04 | 2.7243: Improve air circulation with destratification fans / other methods | $750 | $750 |
$750
20,484
kWh
|
- | |
| 05 | 2.7231: Use radiant heater for spot heating | $245 | $540 |
$245
6,660
kWh
|
- | |
| TOTAL RECOMMENDED | $7,772 | $5,828 |
$5,862
160,136
kWh
|
$1,910
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs