Assessment Year | 2018 |
---|---|
Principal Product | Degrees, certificates, and better futures |
NAICS | 611519: Other Technical and Trade Schools |
SIC | 8249: Vocational Schools, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 54 |
Plant Area |
54,288
ft2
|
Annual Production | 700
units
|
Production Hrs. Annual | 4,380
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $32,305 | 885,920 |
kWh
|
$0.036 | |
Electricity Demand | $30,846 | 2,463 |
kW-mo/yr
|
$12.52 | |
Electricity Fees | $9,951 | - |
|
- | |
Natural Gas | $35,616 | 5,063 |
MMBtu
|
$7.03 | |
Waste Disposal Costs | |||||
Water Usage | $7,626 | 3,268 |
Tgal
|
$2.33 | |
TOTAL YEARLY COSTS | $116,343 | ||||
RECOMMENDED SAVINGS* | $49,772 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $49,772 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7314: Reduce ventilation air | $13,209 | - |
$3,484
95,542
kWh
|
$3,156
-
kW-mo/yr
|
$1,018 |
$5,551
-
MMBtu
|
- | |
02 | 2.7314: Reduce ventilation air | $12,820 | - |
$4,714
129,265
kWh
|
$6,129
-
kW-mo/yr
|
$1,977 | - | - | |
03 | 2.8113: Purchase gas directly from a contract gas supplier | $11,365 | $800 | - | - | - | - | $11,365 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,216 | $11,463 |
$1,781
48,832
kWh
|
$2,598
-
kW-mo/yr
|
$838 | - | - | |
05 | 2.7135: Install occupancy sensors | $4,166 | $2,026 |
$1,396
38,288
kWh
|
$2,094
-
kW-mo/yr
|
$676 | - | - | |
06 | 2.7224: Reduce space conditioning during non-working hours | $2,996 | - | - | - | - |
$2,996
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $49,772 | $14,289 |
$11,374
311,927
kWh
|
$13,977
-
kW-mo/yr
|
$4,509 |
$8,548
-
MMBtu
|
$11,365 | ||
TOTAL IMPLEMENTED | $49,772 | $14,289 |
$11,374
311,927
kWh
|
$13,977
-
kW-mo/yr
|
$4,509 |
$8,548
-
MMBtu
|
$11,365 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs