Assessment Year | 2004 |
---|---|
Principal Product | disposable diapers |
NAICS | 322291: Sanitary Paper Product Manufacturing |
SIC | 2676: Sanitary Paper Products |
Sales Range | $100 M to 500M |
# of Employees | 600 |
Plant Area |
150,000
ft2
|
Annual Production | 200,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,329,049 | 62,458,242 |
kWh
|
$0.021 |
Electricity Demand | $616,492 | 101,205 |
kW-mo/yr
|
$6.09 |
Electricity Fees | $68,490 | - |
|
- |
Natural Gas | $363,950 | 62,077 |
MMBtu
|
$5.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $225,441 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $57,481 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $1,879 | $11,735 |
$1,275
58,258
kWh
|
$604
-
kW-mo/yr
|
- | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,497 | $268 |
$3,054
139,449
kWh
|
$1,443
-
kW-mo/yr
|
- | - | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $16,545 | $2,000 | - | - |
$16,545
-
MMBtu
|
- | |
04 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $91,960 | $12,500 | - | - |
$91,960
-
MMBtu
|
- | |
05 | 2.8114: Change rate schedules or other changes in utility service | $34,560 | - | - | - |
$34,560
-
MMBtu
|
- | |
06 | 3.1161: Eliminate/reduce an operation | $76,000 | $180,000 | - | - | - |
$76,000
-
gal
|
|
TOTAL RECOMMENDED | $225,441 | $206,503 |
$4,329
197,707
kWh
|
$2,047
-
kW-mo/yr
|
$143,065
-
MMBtu
|
$76,000
-
gal
|
||
TOTAL IMPLEMENTED | $57,481 | $14,003 |
$4,329
197,707
kWh
|
$2,047
-
kW-mo/yr
|
$51,105
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs