Assessment Year | 2001 |
---|---|
Principal Product | Chemical Analyses |
NAICS |
n/a
|
SIC | 3829: Measuring and Controlling Devices, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 85 |
Plant Area |
38,000
ft2
|
Annual Production | 94,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $58,921 | 2,244,480 |
kWh
|
$0.026 |
Electricity Demand | $37,912 | 4,584 |
kW-mo/yr
|
$8.27 |
Electricity Fees | $6,319 | - |
|
- |
Natural Gas | $45,540 | 7,642 |
MMBtu
|
$5.96 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $7,811 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $430 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,319 | $5,852 | n/a |
$1,450
47,824
kWh
|
$869
-
kW-mo/yr
|
- |
02 | 2.3212: Optimize plant power factor | $3,545 | $7,155 | n/a | - |
$3,545
-
kW-mo/yr
|
- |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $430 | $430 |
$310
10,100
kWh
|
$120
-
kW-mo/yr
|
- | |
04 | 2.4314: Use synthetic lubricant | $564 | $400 |
$434
14,353
kWh
|
$130
-
kW-mo/yr
|
- | |
05 | 3.4115: Recover and reuse cooling water | $953 | $20 | - | - |
$953
-
gal
|
|
TOTAL RECOMMENDED | $7,811 | $13,857 |
$2,194
72,277
kWh
|
$4,664
-
kW-mo/yr
|
$953
-
gal
|
||
TOTAL IMPLEMENTED | $430 | $430 |
$310
10,100
kWh
|
$120
-
kW-mo/yr
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs