Assessment Year | 2007 |
---|---|
Principal Product | compounded plastic resin |
NAICS | 325991: Custom Compounding of Purchased Resins |
SIC | 3087: Custom Compounding of Purchased Plastics Resins |
Sales Range | $100 M to 500M |
# of Employees | 147 |
Plant Area |
250,000
ft2
|
Annual Production | 170,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,386,556 | 27,138,785 |
kWh
|
$0.051 |
Electricity Demand | $473,863 | 65,156 |
kW-mo/yr
|
$7.27 |
Electricity Fees | $23,149 | - |
|
- |
Natural Gas | $70,379 | 7,242 |
MMBtu
|
$9.72 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $26,181 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,200 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $6,396 | $2,140 |
$5,022
98,299
kWh
|
$1,374
-
kW-mo/yr
|
- | |
02 | 2.2511: Insulate bare equipment | $5,954 | $543 |
$5,954
85,849
kWh
|
- | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,631 | $4,000 |
$2,853
55,838
kWh
|
$778
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,978 | - |
$2,338
45,770
kWh
|
$640
-
kW-mo/yr
|
- | |
05 | 2.3212: Optimize plant power factor | $7,222 | $6,917 | - | - | $7,222 | |
TOTAL RECOMMENDED | $26,181 | $13,600 |
$16,167
285,756
kWh
|
$2,792
-
kW-mo/yr
|
$7,222 | ||
TOTAL IMPLEMENTED | $10,200 | $6,917 |
$2,338
45,770
kWh
|
$640
-
kW-mo/yr
|
$7,222 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs