Assessment Year | 2007 |
---|---|
Principal Product | Recycled Industrial Oil and Metalworking Products |
NAICS | 324191: Petroleum Lubricating Oil and Grease Manufacturing |
SIC | 2992: Lubricating Oils and Greases |
Sales Range | $10 M to 50M |
# of Employees | 25 |
Plant Area |
3,500
ft2
|
Annual Production | 5,000
Tgal
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $158,202 | 1,546,186 |
kWh
|
$0.10 |
Electricity Fees | $493 | - |
|
- |
Natural Gas | $295,886 | 47,200 |
MMBtu
|
$6.27 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $84,990 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $69,798 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $43,338 | - | - | $43,338 | - | |
02 | 2.2511: Insulate bare equipment | $14,251 | $5,900 | - | - |
$14,251
-
MMBtu
|
|
03 | 2.4239: Eliminate or reduce compressed air usage | $10,446 | $890 |
$10,446
101,414
kWh
|
- | - | |
04 | 2.2511: Insulate bare equipment | $6,308 | $6,013 | - | - |
$6,308
-
MMBtu
|
|
05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $4,439 | $1,000 | - | - |
$4,439
-
MMBtu
|
|
06 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $2,752 | $3,415 | - | - |
$2,752
-
MMBtu
|
|
07 | 2.5123: Reduce fluid flow rates | $1,434 | $2,200 | - | - |
$1,434
-
MMBtu
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $913 | $600 |
$913
8,867
kWh
|
- | - | |
09 | 2.2414: Use waste heat from hot flue gases to preheat | $560 | $1,815 | - | - |
$560
-
MMBtu
|
|
10 | 2.7134: Use photocell controls | $549 | $190 |
$549
5,331
kWh
|
- | - | |
TOTAL RECOMMENDED | $84,990 | $22,023 |
$11,908
115,612
kWh
|
$43,338 |
$29,744
-
MMBtu
|
||
TOTAL IMPLEMENTED | $69,798 | $13,703 |
$1,462
14,198
kWh
|
$43,338 |
$24,998
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs