Assessment Year | 2004 |
---|---|
Principal Product | Machine Glazed Paper |
NAICS | 322121: Paper (except Newsprint) Mills |
SIC | 2621: Paper Mills |
Sales Range | $100 M to 500M |
# of Employees | 290 |
Plant Area |
318,000
ft2
|
Annual Production | 32,000
ton
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $612,681 | 26,686,278 |
kWh
|
$0.023 |
Electricity Demand | $235,834 | 52,834 |
kW-mo/yr
|
$4.46 |
Electricity Fees | $8,547 | - |
|
- |
Natural Gas | $122,467 | 24,319 |
MMBtu
|
$5.04 |
Coal | $1,177,963 | 376,000 |
MMBtu
|
$3.13 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $782,781 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Coal Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1331: Burn a less expensive grade of fuel | $542,255 | $2,000,000 | - | - | - | - | $542,255 | |
02 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $145,057 | $125,000 | - | - | - |
$145,057
-
MMBtu
|
- | |
03 | 2.2135: Repair and eliminate steam leaks | $46,000 | $46,000 | - | - | - |
$46,000
-
MMBtu
|
- | |
04 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $24,731 | $30,000 | - | - |
$24,731
-
MMBtu
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,485 | $27,143 |
$9,066
394,868
kWh
|
$2,419
-
kW-mo/yr
|
- | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,777 | $975 |
$7,731
336,145
kWh
|
$2,046
-
kW-mo/yr
|
- | - | - | |
07 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $2,064 | $1,921 | - | - |
$2,064
-
MMBtu
|
- | - | |
08 | 2.7135: Install occupancy sensors | $1,412 | $828 |
$1,412
61,503
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $782,781 | $2,231,867 |
$18,209
792,516
kWh
|
$4,465
-
kW-mo/yr
|
$26,795
-
MMBtu
|
$191,057
-
MMBtu
|
$542,255 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Coal Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs