Assessment Year | 2004 |
---|---|
Principal Product | Molded Plastic Parts |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 105 |
Plant Area |
77,792
ft2
|
Annual Production | 11,000,000
pieces
|
Production Hrs. Annual | 5,760
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $183,657 | 4,707,566 |
kWh
|
$0.039 |
Electricity Demand | $69,601 | 13,800 |
kW-mo/yr
|
$5.04 |
Electricity Fees | $4,344 | - |
|
- |
Natural Gas | $13,485 | 1,830 |
MMBtu
|
$7.37 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $80,855 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $47,250 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7243: Improve air circulation with destratification fans / other methods | $47,250 | $2,600 | - | - | - | $19,250 | $28,000 | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $14,340 | $12,530 | n/a |
$11,301
289,642
kWh
|
$3,039
-
kW-mo/yr
|
- | - | - |
03 | 4.621: Use fixtures to reduce machine changeout times | $7,700 | $800 | - | - | - | $7,700 | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,653 | $9,433 |
$4,410
113,054
kWh
|
$1,243
-
kW-mo/yr
|
- | - | - | |
05 | 2.7135: Install occupancy sensors | $2,270 | $5,610 |
$2,270
58,187
kWh
|
- | - | - | - | |
06 | 2.2511: Insulate bare equipment | $1,281 | $509 |
$1,009
25,861
kWh
|
$272
-
kW-mo/yr
|
- | - | - | |
07 | 2.2437: Recover waste heat from equipment | $1,670 | $500 | - | - |
$1,670
-
MMBtu
|
- | - | |
08 | 2.2514: Cover open tanks | $379 | $500 |
$308
6,772
kWh
|
$71
-
kW-mo/yr
|
- | - | - | |
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $312 | $200 |
$250
6,410
kWh
|
$62
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $80,855 | $32,682 |
$19,548
499,926
kWh
|
$4,687
-
kW-mo/yr
|
$1,670
-
MMBtu
|
$26,950 | $28,000 | ||
TOTAL IMPLEMENTED | $47,250 | $2,600 | - | - | - | $19,250 | $28,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs