| Assessment Year | 2003 |
|---|---|
| Principal Product | Plastic Injection molding |
| NAICS | 326122: Plastics Pipe and Pipe Fitting Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 280 |
| Plant Area |
154,200
ft2
|
| Annual Production | 13,700,000
pieces
|
| Production Hrs. Annual | 7,200
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $478,378 | 12,266,133 |
kWh
|
$0.039 |
| Electricity Demand | $75,854 | 22,986 |
kW-mo/yr
|
$3.30 |
| Electricity Fees | $56,565 | - |
|
- |
| Natural Gas | $73,890 | 9,724 |
MMBtu
|
$7.60 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $67,405 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $11,163 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,775 | $18,691 |
$5,726
146,831
kWh
|
$1,049
-
kW-mo/yr
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,479 | $300 |
$1,296
33,234
kWh
|
$183
-
kW-mo/yr
|
- | |
| 03 | 2.7243: Improve air circulation with destratification fans / other methods | $11,163 | $4,500 |
$(-207.0)
(-5,317)
kWh
|
$(-30.0)
-
kW-mo/yr
|
$11,400
-
MMBtu
|
|
| 04 | 2.4323: Use optimum size and capacity equipment | $6,688 | $8,100 | n/a |
$6,334
162,425
kWh
|
$354
-
kW-mo/yr
|
- |
| 05 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $37,100 | $171,200 |
$(-21,200.0)
(-542,384)
kWh
|
$(-4,500.0)
-
kW-mo/yr
|
$62,800
-
MMBtu
|
|
| 06 | 2.2515: Use optimum thickness insulation | $4,200 | $1,500 |
$3,760
96,533
kWh
|
$440
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $67,405 | $204,291 |
$(-4,291.0)
(-108,678)
kWh
|
$(-2,504.0)
-
kW-mo/yr
|
$74,200
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $11,163 | $4,500 |
$(-207.0)
(-5,317)
kWh
|
$(-30.0)
-
kW-mo/yr
|
$11,400
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs