Assessment Year | 2000 |
---|---|
Principal Product | steel fasteners |
NAICS |
n/a
|
SIC | 3452: Bolts, Nuts, Screws, Rivets, and Washers |
Sales Range | $50 M to 100M |
# of Employees | 145 |
Plant Area |
250,000
ft2
|
Annual Production | 442,000,000
pieces
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $627,865 | 19,549,238 |
kWh
|
$0.032 |
Electricity Demand | $521,532 | 26,748 |
kW-mo/yr
|
$19.50 |
Electricity Fees | $145,071 | - |
|
- |
Natural Gas | $387,921 | 110,053 |
MMBtu
|
$3.52 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $94,254 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,093 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,237 | $9,748 |
$1,156
38,980
kWh
|
$3,081
-
kW-mo/yr
|
- | - | - | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $5,860 | - |
$5,860
197,831
kWh
|
- | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,996 | $1,750 |
$2,482
83,822
kWh
|
$3,514
-
kW-mo/yr
|
- | - | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $13,852 | $13,583 |
$14,708
497,069
kWh
|
$20,819
-
kW-mo/yr
|
- | - | $(-21,675.0) | |
05 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $26,506 | $131,000 | - | - |
$26,506
-
MMBtu
|
- | - | |
06 | 2.2414: Use waste heat from hot flue gases to preheat | $658 | $750 | - | - |
$658
-
MMBtu
|
- | - | |
07 | 3.5111: Filter and reuse hydraulic oil | $37,145 | $10,500 | - | - | - |
$37,145
-
gal
|
- | |
TOTAL RECOMMENDED | $94,254 | $167,331 |
$24,206
817,702
kWh
|
$27,414
-
kW-mo/yr
|
$27,164
-
MMBtu
|
$37,145
-
gal
|
$(-21,675.0) | ||
TOTAL IMPLEMENTED | $16,093 | $11,498 |
$9,498
320,633
kWh
|
$6,595
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs