| Assessment Year | 1996 |
|---|---|
| Principal Product | Motor Vehicle Parts and Assembly |
| NAICS |
n/a
|
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $50 M to 100M |
| # of Employees | 225 |
| Plant Area |
120,000
ft2
|
| Annual Production | 5,000,000
pieces
|
| Production Hrs. Annual | 6,336
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $107,109 | 3,618,406 |
kWh
|
$0.030 |
| Electricity Demand | $143,410 | 8,544 |
kW-mo/yr
|
$16.78 |
| Electricity Fees | $(-4,738.0) | - |
|
- |
| Natural Gas | $20,979 | 4,585 |
MMBtu
|
$4.58 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $43,588 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $13,904 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $2,113 | $1,780 |
$1,105
36,928
kWh
|
$1,008
-
kW-mo/yr
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $24,516 | $61,663 |
$11,759
397,421
kWh
|
$12,757
-
kW-mo/yr
|
- | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $2,084 | $810 |
$1,091
36,928
kWh
|
$993
-
kW-mo/yr
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,091 | $450 |
$6,348
138,628
kWh
|
$3,743
-
kW-mo/yr
|
- | |
| 05 | 2.4237: Substitute compressed air cooling with water or air cooling | $1,700 | $800 |
$989
24,033
kWh
|
$711
-
kW-mo/yr
|
- | |
| 06 | 3.3133: Use other waste concentration methods | $3,084 | - | - | - |
$3,084
-
gal
|
|
| TOTAL RECOMMENDED | $43,588 | $65,503 |
$21,292
633,938
kWh
|
$19,212
-
kW-mo/yr
|
$3,084
-
gal
|
||
| TOTAL IMPLEMENTED | $13,904 | $3,030 |
$8,442
199,589
kWh
|
$5,462
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs