Assessment Year 2026
Principal Product Peanut Butter
NAICS 311911: Roasted Nuts and Peanut Butter Manufacturing
SIC 2099: Food Preparations, Not Elsewhere Classified
Sales Range $100
M
to 500
M
# of Employees 300
Plant Area 162,000
ft2
Annual Production 170,000,000
lb
Production Hrs. Annual 8,760
hrs
Location (State) Kentucky

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $560,476 17,217,000
kWh
Electricity Demand $692,696 33,354
kW-mo/yr
Electricity Fees $114,542 -
Natural Gas $356,112 67,725
MMBtu
Other Gas $35,505 1
MMBtu
TOTAL YEARLY COSTS $1,759,331
RECOMMENDED SAVINGS* $123,620 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.7135: Install occupancy sensors $269 $106 $269
8,278
kWh
- -
02 2.7243: Improve air circulation with destratification fans / other methods $6,794 $10,000 $6,794
208,710
kWh
- -
03 2.4231: Reduce the pressure of compressed air to the minimum required $4,621 - $4,621
135,435
kWh
- -
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,937 $945 $1,937
59,432
kWh
- -
05 2.2692: Use outside cold water source as a supply of cooling water $43,299 $98,575 $18,208
558,514
kWh
$25,091
-
kW-mo/yr
-
06 2.2437: Recover waste heat from equipment $35,971 $32,500 - - $35,971
-
MMBtu
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,278 $2,850 $1,278
39,212
kWh
- -
08 2.9114: Use solar heat to make electricty $29,450 $438,603 $13,694
420,666
kWh
$15,756
-
kW-mo/yr
-
TOTAL RECOMMENDED $123,620 $583,579 $46,802
1,430,247
kWh
$40,847
-
kW-mo/yr
$35,971
-
MMBtu
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs