| Assessment Year | 2026 |
|---|---|
| Principal Product | Aging Barrels |
| NAICS | 321920: Wood Container and Pallet Manufacturing |
| SIC | 2449: Wood Containers, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
139,100
ft2
|
| Annual Production | 450,000
units
|
| Production Hrs. Annual | 4,000
hrs
|
| Location (State) | Kentucky |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $588,397 | 9,265,200 |
kWh
|
$0.064 | |
| Electricity Demand | $170,837 | 23,760 |
kW-mo/yr
|
$7.19 | |
| Electricity Fees | $171,706 | - |
|
- | |
| Natural Gas | $135,528 | 12,000 |
MMBtu
|
$11.29 | |
| Other Energy | $18,378 | 1 |
MMBtu
|
$18,378.00 | |
| Waste Disposal Costs | |||||
| Water Usage | $191,027 | 9,629,700 |
Tgal
|
$0.020 | |
| TOTAL YEARLY COSTS | $1,275,873 | ||||
| RECOMMENDED SAVINGS* | $101,769 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,977 | - |
$1,977
31,125
kWh
|
- | - | |
| 02 | 2.2437: Recover waste heat from equipment | $6,266 | $25,000 | - | - |
$6,266
-
MMBtu
|
|
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $30,023 | $55,088 |
$30,023
472,765
kWh
|
- | - | |
| 04 | 2.9114: Use solar heat to make electricty | $63,503 | $907,925 |
$52,211
822,141
kWh
|
$11,292
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $101,769 | $988,013 |
$84,211
1,326,031
kWh
|
$11,292
-
kW-mo/yr
|
$6,266
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs