| Assessment Year | 2025 | 
|---|---|
| Principal Product | Genomics | 
| NAICS | 325180: Other Basic Inorganic Chemical Manufacturing | 
| SIC | 8732: Commercial Economic, Sociological, and Educational Research | 
| Sales Range | $10 M  to 50M  | 
    
| # of Employees | 90 | 
| Plant Area | 
                            75,000
                 
ft2
 
                     | 
    
| Annual Production | 1,500,000
             
units
 
         | 
    
| Production Hrs. Annual | 2,652
             
hrs
 
         | 
    
| Location (State) | Kentucky | 
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $107,395 | 3,014,800 | 
             
kWh
 
         | 
        $0.036 | 
| Electricity Demand | $155,064 | 5,389 | 
             
kW-mo/yr
 
         | 
        $28.77 | 
| Electricity Fees | $17,107 | - | 
             | 
        - | 
| Natural Gas | $65,758 | 8,195 | 
             
MMBtu
 
         | 
        $8.02 | 
| TOTAL YEARLY COSTS | $345,324 | |||
| RECOMMENDED SAVINGS* | $66,798 | 
             See individual recommendations below 
            *Non-energy impacts included in savings.
         | 
    ||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | 
|---|---|---|---|---|---|---|---|---|
| 01 | 2.8114: Change rate schedules or other changes in utility service | $41,000 | - | - | - | $41,000 | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,475 | $3,938 | 
                        $2,475
                                                     69,515
                                 
                                            
kWh
 
                             | 
                                                                                - | - | - | |
| 03 | 2.9114: Use solar heat to make electricty | $11,054 | $88,745 | 
                        $4,430
                                                     124,436
                                 
                                            
kWh
 
                             | 
                                                                                
                        $6,624
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                                                                - | - | |
| 04 | 2.7226: Use computer programs to optimize hvac performance | $11,076 | $19,500 | 
                        $6,869
                                                     192,947
                                 
                                            
kWh
 
                             | 
                                                                                - | - | 
                        $4,207
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    |
| 05 | 2.7311: Ventilation system to shut off when room is not in use | $1,193 | - | 
                        $1,193
                                                     33,503
                                 
                                            
kWh
 
                             | 
                                                                                - | - | - | |
| TOTAL RECOMMENDED | $66,798 | $112,183 | 
                        $14,967
                                                     420,401
                                 
                                            
kWh
 
                             | 
                                                                                
                        $6,624
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                                                                $41,000 | 
                        $4,207
                                                     -
                                 
                                            
MMBtu
 
                             | 
                                    ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs