Assessment Year | 2025 |
---|---|
Principal Product | Polymer Films |
NAICS | 333242: Semiconductor Machinery Manufacturing |
SIC | 3674: Semiconductors and Related Devices |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
57,548
ft2
|
Annual Production | 973
ton
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $171,007 | 3,095,581 |
kWh
|
$0.055 |
Electricity Demand | $194,157 | 8,613 |
kW-mo/yr
|
$22.54 |
Electricity Fees | $18,894 | - |
|
- |
Natural Gas | $6,840 | 937 |
MMBtu
|
$7.30 |
TOTAL YEARLY COSTS | $390,898 | |||
RECOMMENDED SAVINGS* | $98,729 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,366 | - |
$1,366
24,726
kWh
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,535 | $1,080 |
$2,535
45,932
kWh
|
- | |
03 | 2.2692: Use outside cold water source as a supply of cooling water | $34,574 | $58,425 |
$20,291
367,585
kWh
|
$14,283
-
kW-mo/yr
|
|
04 | 2.9114: Use solar heat to make electricty | $57,929 | $431,966 |
$32,664
591,294
kWh
|
$25,265
-
kW-mo/yr
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,723 | $561 |
$1,088
19,710
kWh
|
$635
-
kW-mo/yr
|
|
06 | 2.7135: Install occupancy sensors | $602 | $2,234 |
$602
10,912
kWh
|
- | |
TOTAL RECOMMENDED | $98,729 | $494,266 |
$58,546
1,060,159
kWh
|
$40,183
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs