| Assessment Year | 2025 | 
|---|---|
| Principal Product | Phenol Resins | 
| NAICS | 325211: Plastics Material and Resin Manufacturing | 
| SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers | 
| Sales Range | $100 Mto 500 M | 
| # of Employees | 140 | 
| Plant Area | 2,800,000 
ft2
 | 
| Annual Production | 111,457 
ton
 | 
| Production Hrs. Annual | 5,880 
hrs
 | 
| Location (State) | Kentucky | 
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,310,577 | 40,762,397 | 
kWh
 | $0.032 | 
| Electricity Demand | $1,404,108 | 66,222 | 
kW-mo/yr
 | $21.20 | 
| Electricity Fees | $164,074 | - |  | - | 
| Natural Gas | $2,007,896 | 561,817 | 
MMBtu
 | $3.57 | 
| TOTAL YEARLY COSTS | $4,886,655 | |||
| RECOMMENDED SAVINGS* | $76,300 | See individual recommendations below*Non-energy impacts included in savings. | ||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | 
|---|---|---|---|---|---|---|
| 01 | 2.7135: Install occupancy sensors | $1,784 | $3,182 | $1,784 55,417
                                 
kWh
 | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,935 | $5,846 | $3,539 109,897
                                 
kWh
 | $3,396 -
                                 
kW-mo/yr
 | |
| 03 | 2.2692: Use outside cold water source as a supply of cooling water | $32,007 | $43,234 | $13,644 424,368
                                 
kWh
 | $18,363 -
                                 
kW-mo/yr
 | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $965 | $525 | $965 29,971
                                 
kWh
 | - | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,101 | $4,725 | $2,101 65,267
                                 
kWh
 | - | |
| 06 | 2.9114: Use solar heat to make electricty | $32,508 | $321,604 | $14,816 460,812
                                 
kWh
 | $17,692 -
                                 
kW-mo/yr
 | |
| TOTAL RECOMMENDED | $76,300 | $379,116 | $36,849 1,145,732
                                 
kWh
 | $39,451 -
                                 
kW-mo/yr
 | ||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs
             
             
             
            