| Assessment Year | 2025 |
|---|---|
| Principal Product | Fabricated Metal |
| NAICS | 332710: Machine Shops |
| SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 100 |
| Plant Area |
70,000
ft2
|
| Annual Production | 987
units
|
| Production Hrs. Annual | 2,500
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $81,600 | 716,680 |
kWh
|
$0.11 |
| Electricity Demand | $763 | 4,257 |
kW-mo/yr
|
$0.18 |
| Electricity Fees | $5,379 | - |
|
- |
| Natural Gas | $29,461 | 3,181 |
MMBtu
|
$9.26 |
| TOTAL YEARLY COSTS | $117,203 | |||
| RECOMMENDED SAVINGS* | $80,869 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,769 | $3,240 |
$3,769
33,104
kWh
|
- | |
| 02 | 2.9114: Use solar heat to make electricty | $71,181 | $417,175 |
$70,987
623,465
kWh
|
$194
-
kW-mo/yr
|
|
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,413 | $9,750 |
$4,413
38,742
kWh
|
- | |
| 04 | 2.7135: Install occupancy sensors | $1,506 | $185 |
$1,506
13,225
kWh
|
- | |
| TOTAL RECOMMENDED | $80,869 | $430,350 |
$80,675
708,536
kWh
|
$194
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs